You are hereComponent products / Power converter, regulation, and conditioning boards / PSM Power Supply Monitor for 12 VDC Solar Applications

PSM Power Supply Monitor for 12 VDC Solar Applications


Last changed July 9, 2007 - 3:08pm

Overview

Automation and Electronics, Inc. Power Supply Monitor (PSM)Power Supply MonitorThe PSM Power Supply Monitor module is designed to provide an AC power failure, DC power failure, load shed and low battery signal from an incoming AC power line and a 24 VDC or 12 VDC backup battery power supply.

Specifications

The PSM module is designed with standard plug-in solid state I/O modules to monitor the AC and DC power fail signals. A power monitor IC is used to generate the low battery signal along with the load shed signal.

Mechanical
Size: 3" x 3-1/2" PC board
Mounting: Snap track

AC Power Fail
120 VAC I/O module IAC-24
Input range: 90 to 140 VAC
Maximum input current: 11 mA
Dropout voltage: 25 Vrms
DC output supply: 15 to 30 VDC, 24 Vnominal
Maximum output load (35 deg. C): 40 mA
120 VAC I/O module IAC-15
Input range: 90 to 140 VAC
Maximum input current: 11 mA
Dropout voltage: 25 Vrms
DC output supply: 8 to 18 VDC, 15 Vnominal
Maximum output load (35 deg. C): 30 mA


240 VAC I/O module IAC24A
Input range: 180 to 280 VAC
Maximum input current: 6 mA
Dropout voltage: 50 Vrms
DC output supply: 15 to 30 VDC, 24 Vnominal
Maximum output load (35 deg. C) 40 mA
240 VAC I/O module: IAC15A
Input range 180 to 280 VAC
Maximum input current: 6 mA
Dropout voltage: 50 Vrms
DC output supply: 8 to 18 VDC, 15 Vnominal
Maximum output load (35 deg. C): 30 mA


DC Power Fail
24 VDC /12 VDC I/O Module IDC24
Input range: 3 to 32 VDC
Maximum input current: 14 mA
Dropout voltage: 1 VDC
DC output supply: 15 to 30 VDC, 24 Vnominal
Maximum output load (35 deg. C): 50 mA
24 VDC /12 VDC I/O Module IDC15
Input range: 3 to 32 VDC
Maximum input current: 14 mA
Dropout voltage: 1 VDC
DC output supply: 8 to 18 VDC, 15 Vnominal
Maximum output load (35 deg. C): 40 mA


Thresholds
Voltage Monitor 24 VDC
Low battery detect: 22.5 VDC
Restore: 23.8 VDC
Load shed: 20.5 VDC
Restore: 23.3 VDC
Voltage Monitor 12 VDC
Low battery detect: 11.25 VDC
Restore: 11.9 VDC
Load shed: 10.25 VDC
Restore: 11.65 VDC


Download PDF