You are hereComponent products / Surge protection and signal conditioning boards / GT-1420 4-20 mA Analog Loop Surge Protection Module

GT-1420 4-20 mA Analog Loop Surge Protection Module


Last changed May 23, 2007 - 12:33pm

Overview

The GT-1420 provides in-line surge protection for the 4-20 mA 24 VDC analog inputs of chart recorders, meters, PLC's, etcetera.

The analog input signal is protected with a combination of series resistance, a 90 V gas tube, series inductance, and 31 V metal oxide varistor.

Specifications

Mechanical
Size: 1-3/4" x 1-5/32" PC board
Mounting: Velcro® strip
Inputs One
Gas tube: DC Spark over voltage 90 VDC
Inductor: 680 uH, 12.25 Ohm
Terminals: 200 V barrier
Resistance: 10 Ohm, 1/2 W
Metal Oxide Varistor (MOV)
Maximum input working voltage: 31 VDC
Maximum clamping voltage: 79 VDC @ 5 A IP
Peak current: 250 A (8/20 uS)
Transient protection Meets or exceeds IEEE 472.1974 surge withstand capacity (SWC) tests (ANSI C27.30a-1974)

Consult the factory for optional voltages.