You are hereComponent products / Surge protection and signal conditioning boards / GT-3424 24 VDC Digital Input Gas Tube Protection Module

GT-3424 24 VDC Digital Input Gas Tube Protection Module


Last changed May 23, 2007 - 12:34pm

Overview

The GT-3424 provides gas tube protection for up to sixteen single ended inputs, as normally used with 24 VDC digital inputs.

The field inputs are terminated at 300 V barrier terminals, and further protected by a parallel combination of 90 V gas tubes, series inductance, and 31 V MOVs in parallel. The protected signal lines are then available for connection to low voltage electronic circuits via terminal blocks or mass termination connectors.

Specifications

Mechanical
Size: 3" x 6.8" PC board
Mounting: Snap track
Inputs Sixteen, single ended
Gas tubes: 90 VDC breakdown typical
Series inductor: 680 uH
Metal oxide varistor (MOV)
Maximum input working voltage: 31 VDC
Maximum clamping voltage: 79 VDC @ 51 pA (8/20) uH sec
Peak current: 250 A
Transient protection Meets or exceeds IEEE 472.1974 surge withstand capacity (SWC) tests (ANSI C37.901974)

Download PDF